 EMC filters
2-line filters
for converters and power electronics
Rated current 10 to 60 A
Series/Type: Date: B84142A*R000, G075 January 2006
EPCOS AG 2006. Reproduction, publication and dissemination of this data sheet and the information contained therein without EPCOS' prior express consent is prohibited.
2-line filters for converters and power electronics
Power line filters for 1-phase systems Rated voltage 250 V DC/AC, 50/60 Hz Rated current 10 to 60 A Construction
2-line filters Metal case
B84142A*R000, G075
Features

High insertion loss
Easy to install
Degree of protection IP 201) for *R000
Very compact design
Optimized for long motor cables
and operation under full load ENEC10, UL and cUL approval Applications
Frequency converters for motor drives, e.g.
- elevators - conveyor systems - pumps - traction systems - HVAC systems (heating, ventilation and air conditioning) Power supplies DC applications Terminals
Finger-safe terminal blocks Screw thread M6
Marking Marking on component: Manufacturer's logo, ordering code, rated voltage, rated current, rated temperature, climatic category, terminal assignment, date code Minimum marking on packaging: Manufacturer's logo, ordering code
1) To IEC 60529
Please read Cautions and warnings and
Important notes at the end of this document.
2
01/06
2-line filters for converters and power electronics
Typical circuit diagram
LINE L LOAD L'
B84142A*R000, G075
N
N'
SSB1515-U
Technical data and measuring conditions Rated voltage VR Rated current IR Test voltage Vtest Overload capability (thermal) Leakage current Ileak Climatic category (IEC 60068-1) Approvals 250 V DC/AC, 50/60 Hz Referred to 40 C ambient temperature 1770 V DC, 2 s (line/line) 2700 V DC, 2 s (lines/case) 1.5 * IR for 3 min per hour or 2.5 * IR for 30 s per hour At 250 V AC, 50 Hz R000: 25/100/21 (-25 C/+100 C/21 days damp heat test) G075: 25/085/21 (-25 C/+85 C/21 days damp heat test) EN 133200, UL 1283, CSA C22.2 No.8
Characteristics and ordering codes VR AC/DC V 250 IR A 10 20 30 40 50 60 60 Terminal Ileak cross section mm2 4 4 6 6 16 16 Screw stud M6 < 26 1.4 2.5 B84142A0060G075 -- -- mA <8 <8 <8 < 17 < 26 < 26 Rtyp m 18 10 5 3.6 1.8 1.4 Approx. weight kg 0.55 1.0 1.0 1.0 2.5 2.5 B84142A0010R000 B84142A0020R000 B84142A0030R000 B84142A0040R000 B84142A0050R000 B84142A0060R000 x x x x x x x x x x x x Ordering code Approvals
x = approval granted
Please read Cautions and warnings and
Important notes at the end of this document.
3
01/06
2-line filters for converters and power electronics
Dimensional drawings B84142A0010R000 (10 A)
_ 0.6 44.5 +1
B84142A*R000, G075
30
19 0.80.1
7.5 50.8 70
101.60.3 PE M4 x 15 Marking LINE LOAD o4.70.1 133 154.8
_ 0.5 60.4 +0.1
Terminal blocks 4 mm 2 Tightening torque 0.6 ... 0.8 Nm
SSB1522-C-E
B84142A0020R000 (20 A)
4.30.1
50.80.3 Terminal blocks 4 mm 2 Tightening torque 0.6 ... 0.8 Nm 6.3 351 Terminal blocks 4 mm 2 Tightening torque 0.6 ... 0.8 Nm
0.80.1
PE M5 x 20
105
Marking LINE LOAD
_ 0.5 95.2 +0.1
20
11
161
241 351
99 121+1
241 _ 0.6 68 +1
84
SSB1523-K-E
Please read Cautions and warnings and
Important notes at the end of this document.
4
01/06
2-line filters for converters and power electronics
B84142A0030R000, B84142A0040R000 (30 and 40 A)
Terminal blocks 6 mm 2 Tightening
torque 1.5 ... 1.8 Nm
50.80.3 6.3
B84142A*R000, G075
4.30.1
401 0.80.1
Terminal
blocks 6 mm 2
Tightening torque 1.5 ... 1.8 Nm
105
LINE LOAD
PE M5 x 20
241 401
161
99 130
241
_ 0.6 68 +1
SSB1524-T-E
B84142A0050R000, B84142A0060R000 (50 and 60 A)
84
131
36 85
Marking
_ 0.5 95.2 +0.1
20
11
1+0.1
42
180
1150.2
Terminal blocks 16 mm 2 Tightening torque 2 ... 2.3 Nm
1000.3
Marking
Line
Load
6.6
PE M6 x 25
SSB1525-2-E
245
Please read Cautions and warnings and
Important notes at the end of this document.
5
01/06
115
17
60
2-line filters for converters and power electronics
B84142A0060G075 (60 A)
24
B84142A*R000, G075
13
13
23 180 1150.3
1
25 85
Terminal stud M6 Marking LINE LOAD
1000.3
6.6
PE M6 x 24
115
SSB2183-9-E
Please read Cautions and warnings and
Important notes at the end of this document.
6
01/06
15
60
2-line filters for converters and power electronics
Insertion loss (typical values at Z = 50 ) unsymmetrical, adjacent branches terminated common mode, all branches in parallel (asymmetrical) differential mode (symmetrical) Filters for 10 A
120 dB 100
SSB1516-3
B84142A*R000, G075
Filters for 20 A
120 dB B84142A0020R000 100
SSB1517-B
80
80
60
60
40
40
20 B84142A0010R000 04 10 10 5 10 6
20
10 7
Hz 10 8 f
04 10
10 5
10 6
10 7
Hz 10 8 f
Filters for 30 A
120 dB B84142A0030R000 100
SSB1518-J
Filters for 40 A
120 dB B84142A0040R000 100
SSB1519-S
80
80
60
60
40
40
20
20
04 10
10 5
10 6
10 7
Hz 10 8 f
04 10
10 5
10 6
10 7
Hz 10 8 f
Please read Cautions and warnings and
Important notes at the end of this document.
7
01/06
2-line filters for converters and power electronics
Insertion loss (typical values at Z = 50 ) unsymmetrical, adjacent branches terminated common mode, all branches in parallel (asymmetrical) differential mode (symmetrical) Filters for 50 A
120 dB 100
SSB1520-V
B84142A*R000, G075
Filters for 60 A
B84142A0050R000
120 dB 100
SSB1521-4
B84142A0060R000 B84142A0060G075
80
80
60
60
40
40
20
20
04 10
10 5
10 6
10 7
Hz 10 8 f
04 10
10 5
10 6
10 7
Hz 10 8 f
Please read Cautions and warnings and
Important notes at the end of this document.
8
01/06
EMC filters Cautions and warnings
Important information Please read all safety and warning notes carefully before installing the EMC filter and putting it into ). The same applies to the warning signs on the filter. Please ensure that the signs operation (see are not removed nor their legibility impaired by external influences. Death, serious bodily injury and substantial material damage to equipment may occur if the appro priate safety measures are not carried out or the warnings in the text are not observed. Using according to the terms The EMC filters may be used only for their intended application within the specified values in low voltage networks in compliance with the instructions given in the data sheets and the data book. The conditions at the place of application must comply with all specifications for the filter used. Warnings
It shall be ensured that only qualified persons (electricity specialists) are engaged on work such

as planning, assembly, installation, operation, repair and maintenance. They must be provided with the corresponding documentation. Danger of electric shock. EMC filters contain components that store an electric charge. Danger ous voltages can continue to exist at the filter terminals for longer than five minutes even after the power has been switched off. The protective earth connections shall be the first to be made when the EMC filter is installed and the last to be disconnected. Depending on the magnitude of the leakage currents, the particular specifications for making the protective-earth connection must be observed. Impermissible overloading of the EMC filter, such as impermissible voltages at higher frequen cies that may cause resonances etc. can lead to destruction of the filter housing. EMC filters must be protected in the application against impermissible exceeding of the rated currents by suitable overcurrent protective.
9
01/06
EMC filters Important notes
The following applies to all products named in this publication: 1. Some parts of this publication contain statements about the suitability of our products for certain areas of application. These statements are based on our knowledge of typical requirements that are often placed on our products in the areas of application concerned. We nevertheless expressly point out that such statements cannot be regarded as binding statements about the suitability of our products for a particular customer application. As a rule, EPCOS is either unfamiliar with individual customer applications or less familiar with them than the customers themselves. For these reasons, it is always ultimately incumbent on the customer to check and decide whether an EPCOS product with the properties described in the product specification is suitable for use in a particular customer application. 2. We also point out that in individual cases, a malfunction of passive electronic components or failure before the end of their usual service life cannot be completely ruled out in the current state of the art, even if they are operated as specified. In customer applications requiring a very high level of operational safety and especially in customer applications in which the malfunction or failure of a passive electronic component could endanger human life or health (e.g. in accident prevention or life-saving systems), it must therefore be ensured by means of suitable design of the customer application or other action taken by the customer (e.g. installation of protective circuitry or redundancy) that no injury or damage is sustained by third parties in the event of malfunction or failure of a passive electronic component. 3. The warnings, cautions and product-specific notes must be observed. 4. In order to satisfy certain technical requirements, some of the products described in this publication may contain substances subject to restrictions in certain jurisdictions (e.g. because they are classed as "hazardous"). Useful information on this will be found in our Material Data Sheets on the Internet (www.epcos.com/material). Should you have any more detailed questions, please contact our sales offices. 5. We constantly strive to improve our products. Consequently, the products described in this publication may change from time to time. The same is true of the corresponding product specifications. Please check therefore to what extent product descriptions and specifications contained in this publication are still applicable before or when you place an order. We also reserve the right to discontinue production and delivery of products. Consequently, we cannot guarantee that all products named in this publication will always be available. 6. Unless otherwise agreed in individual contracts, all orders are subject to the current version of the "General Terms of Delivery for Products and Services in the Electrical Industry" published by the German Electrical and Electronics Industry Association (ZVEI). 7. The trade names EPCOS, EPCOS-Jones, Baoke, CeraDiode, CSSP, MLSC, PhaseCap, PhaseMod, SIFI, SIKOREL, SilverCap, SIMID, SIOV, SIP5D, SIP5K, UltraCap, WindCap are trademarks registered or pending in Europe and in other countries. Further information will be found on the Internet at www.epcos.com/trademarks.
10
01/06


▲Up To Search▲   

 
Price & Availability of B84142A0040R000

All Rights Reserved © IC-ON-LINE 2003 - 2022  

[Add Bookmark] [Contact Us] [Link exchange] [Privacy policy]
Mirror Sites :  [www.datasheet.hk]   [www.maxim4u.com]  [www.ic-on-line.cn] [www.ic-on-line.com] [www.ic-on-line.net] [www.alldatasheet.com.cn] [www.gdcy.com]  [www.gdcy.net]


 . . . . .
  We use cookies to deliver the best possible web experience and assist with our advertising efforts. By continuing to use this site, you consent to the use of cookies. For more information on cookies, please take a look at our Privacy Policy. X